What to say when you review concrete removal: the extent, the exposed reinforcing, and how the work is done.

Concrete slab removed down to the exposed reinforcing steel mesh during a condominium slab repair

Say it like this

Talk the way you would to a colleague on site. Below each recording is the note Neuveria writes from it. You review and edit every note before the report goes out.

Extent of removal

You say

“Slab removal at the courtyard between units one fifty-five and one sixty-one. Topping's removed down to the structural slab over about eighteen by forty feet. Top mat is exposed, fifteen M at about ten inches. Bars are mostly in good shape, light surface rust only. Shoring is in below on P one.”

Neuveria writes

Slab removal was reviewed at the courtyard between units 155 and 161. The topping was removed down to the structural slab over an area approximately 5.5 m x 12.2 m (18'-0" x 40'-0"). The top reinforcement mat was exposed and consisted of 15M bars at approximately 255 mm (10") spacing. The bars were generally in good condition, with light surface rust only. Shoring was in place below on Level P1.

Section loss

You say

“At the north end, about six top bars over maybe five feet have section loss, some lost around a third of the diameter. This is outstanding. Contractor to add new fifteen M bars lapped about two feet, and we'll review before the pour.”

Neuveria writesOutstanding

At the north end, approximately six top bars over a length of approximately 1.52 m (5'-0") exhibited section loss, with some having lost approximately one-third of their diameter. This item remains outstanding. The contractor is to install new 15M bars with laps of approximately 0.61 m (2'-0"). We will review the bars before the concrete pour.

Breaker too heavy

You say

“Near grid three they were using a sixty pound breaker on the slab. Spec says thirty pound max. That's non-compliant. We told them to switch to the smaller hammer and check the underside of the slab on P one for any damage.”

Neuveria writesNon-compliant

Near grid line 3, the contractor was using a 27 kg (60 lb) breaker on the slab. The specification limits the breaker weight to 14 kg (30 lb) maximum; therefore, the equipment did not comply with the specification. We instructed the contractor to use the smaller breaker and review the underside of the slab on Level P1 for damage.